4-18
4-2 Function Mode
4
Func
tions
External DC Injection Braking (A051 = 00)
•Allocate 07 (DB) to the desired multi-function input. DC injection braking can be applied by turning
on/off the DB terminal, regardless of the DC injection braking selection (A051).
•Set the DC injection braking power in A054.
•If the DC injection braking delay time (A053) is set, the Inverter output will be shut off during the
specified time period and the motor goes into free-run status. After the set time elapses, DC
injection braking starts.
•Set the DC injection braking time (A055) or the DB setting while taking into account motor heat
generation. Long continuous use of DB may cause the motor to burn out.
•Perform each setting according to your system after selecting the level or edge operation in A056
Data
Symbol
Function name
Status
Description
07
DB
External DC injection braking
ON
DC injection braking is performed
during deceleration.
OFF
DC injection braking is not performed
during deceleration.
Related parameters
C001 to C005
(a) Edge operation (A056: 00)
(b) Level operation (A056: 01)
(Example 1-a)
(Example 1-b)
(Example 2-a)
(Example 2-b)
(Example 3-a)
(Example 3-b)
FW
DB
Output frequency
A055
FW
DB
Output frequency
FW
DB
Output frequency
A055
FW
DB
Output frequency
FW
DB
Output frequency
A055
A053
Free running
FW
DB
Output frequency
A053
Free running
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......