3-24
3-6 Parameter List
3
Operation
Non-
stop
at momentar
y po
wer interr
uption
b053
Deceleration time of
non-stop function at
momentary power
interruption
0.01 to 99.99
100.0 to 999.9
1000 to 3000
1.0
No
s
10CC
4-36
b054
Deceleration starting
width of non-stop
function at
momentary power
interruption
0.0 to 10.0
0.0
No
Hz
10CE
4-36
Others
b055
Overvoltage
protection
proportional gain
during deceleration
0.2 to 5.0
0.2
Yes
⎯
1173
4-37
b056
Overvoltage
protection integral
time during
deceleration
0.0 to 150.0
0.2
Yes
s
1174
4-37
b080
AM adjustment
0. to 255.
(Shared with C086 for AM offset adjustment)
100.
Yes
⎯
10CF
4-39
4-62
b082
Starting frequency
0.5 to 9.9
1.5
No
Hz
10D1
4-39
b083
Carrier frequency
2.0 to 12.0
3.0
No
kHz
10D2
4-40
4-63
Initial
izati
on
b084 Initialization selection
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes data
00
No
⎯
10D3
4-41
b085
Initialization
parameter selection
00
* Do not change.
00
No
⎯
10D4
4-41
Othe
rs
b086
Frequency
conversion
coefficient
0.1 to 99.9
1.0
Yes
⎯
10D5
4-41
b087
STOP key selection
00: Enabled
01: Disabled
00
No
⎯
10D6
4-41
b088
Free-run stop
selection
00: 0 Hz start
01: Active Frequency Matching restart
00
No
⎯
10D7
4-41
b089
Monitor display
selection
01: Output frequency monitor
02: Output current monitor
03: Rotation direction monitor
04: PID feedback value monitor
05: Multi-function input monitor
06: Multi-function output monitor
07: Frequency conversion monitor
01
Yes
⎯
10D8
4-42
b091
Stop selection
00: Deceleration
→
Stop
01: Free-run stop
00
No
⎯
10DA
4-41
b092
Cooling fan control
00: Always ON
01: ON during RUN
02: Depends on the fin temperature
01
No
⎯
10DB
4-43
b130
Overvoltage LAD
stop function
00: Disabled
01: Enabled
00
No
⎯
10F5
4-38
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Change
during
Run
Unit
Modbus
Address
(Hex)
Page
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......