4-55
4-2 Function Mode
4
Functions
Multi-function Output Terminal Selection
•You can allocate the following functions to multi-function output terminal 11 and the relay output
terminals.
•While the multi-function output terminal 11 selection is for open collector output (allocated in
C021), the relay output (AL2, AL1) function selection is for SPDT-contact relay output (allocated in
C026).
•You can select NO- or NC-contact output for each output terminal with C031 or C036.
Signal During RUN
This function outputs a signal while the Inverter is running.
Parameter No.
Function name
Data
Default setting
Unit
C021
Multi-function output
terminal 11 selection
00: RUN (signal during RUN)
01: FA1 (constant speed arrival signal)
02: FA2 (over set frequency arrival signal)
03: OL (overload warning)
04: OD (excessive PID deviation)
05: AL (alarm output)
06: Dc (disconnection detection)
07: FBV (PID FB status output)
08: NDc (network error)
09: LOG (logic operation output)
10: ODc (Do not use.)
43: LOC (light load detection signal)
00
⎯
C026
Relay output (AL2,
AL1) function selection
05
⎯
Data
Description
Reference item
Page
00
RUN: Signal during RUN
Signal during RUN
4-55
01
FA1: Constant speed arrival signal
Frequency arrival signal
4-56
02
FA2: Over set frequency arrival
signal
03
OL: Overload warning
Overload warning signal
4-33
04
OD: Excessive PID deviation
Excessive PID deviation output
4-22
05
AL: Alarm output
Alarm output
4-57
06
Dc: Disconnection detection
External analog input
disconnection detection
4-58
07
FBV: PID FB status output
PID FB status output
4-22
08
NDc: Network error
Network error
4-58
09
LOG: Logic operation output
Logic operation result output
4-59
10
ODc: Not used.
—
—
43
LOC: Light load detection signal
Light load detection signal
4-60
Data
Symbol
Function name
Status
Description
00
RUN
Signal during RUN
ON
The Inverter is in RUN mode.
OFF
The Inverter is in STOP mode.
Available output terminals
11-CM2, AL2-AL0 (or AL1-AL0)
Required settings
C021, C026
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......