2-2 Wiring
2
De
sign
Wiring to the Power Supply and Motor
•Do not connect the power supply other than to R/L1, S/L2, or T/L3.
•Do not remove the short-circuit bar between P/+2 and +1, except when a DC reactor is connected.
Note 1: Install an earth leakage breaker on the power supply input side.
(Select an earth leakage breaker having a higher sensed leakage current and avoid
unnecessary operation.)
If the wiring between the Inverter and the motor is too long (longer than 10 m), the motors
thermal relay may malfunction due to harmonics. Install an AC reactor on the Inverter output
side, or use a current sensor instead of the motors thermal relay.
R/L1 S/L2 T/L3
Power supply
Ground
U/T1 V/T2
W/T3
N/- P/+
+1
Motor
Motor
earth
Main circuit terminal block (input side)
Main circuit terminal block (output side)
(Example) JX-A2004
R/L1 S/L2 T/L3
Power supply
Ground
U/T1 V/T2
W/T3 N/- P/+
+1
Motor
earth
Motor
Main circuit terminal block (input side)
Main circuit terminal block (output side)
(Example) JX-A2037
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......