H3DR-A/P/M
H3DR-A/P/M
68
Ratings
NPN (No-voltage) Input Models
Item
H3DR-A
H3DR-AS
H3DR-P
Rated supply
voltage
100 to 240 VAC (50/60 Hz),
12 VDC,
24 VDC/VAC (50/60 Hz)
12 VDC,
24 VDC/VAC (50/60 Hz)
100 to 120 VAC (50/60 Hz),
200 to 240 VAC (50/60 Hz),
24 VDC/VAC (50/60 Hz)
Operating
voltage range
85% to 110% of rated supply voltage (90% to 110% with 12-VDC type)
85% to 110% of rated supply voltage
Power reset
Minimum power-opening time: 0.1 s
No-voltage
input
ON impedance:
1 k
$
max.
ON residual voltage: 1 V max.
OFF impedance:
100 k
$
min.
Power
consumption
100 to 240 VAC: approx. 8 VA
12 VDC:
approx. 0.4 W
24 VDC/VAC:
approx. 1.3 VA (AC)
approx. 0.6 W (DC)
100 to 120 VAC: approx. 6 VA
200 to 240 VAC: approx. 10 VA
24 VDC/VAC:
approx. 2 VA (AC)
approx. 1 W (DC)
Control
outputs
Contacts: 5 A at 250 VAC, resistance
load (cos
%
= 1)
Transistor output: Open collector
(NPN/PNP),
100 mA max. at
30 VDC max.,
residual voltage:
2 V max.
Contacts: 5 A at 250 VAC, resistance
load (cos
%
= 1)
Ambient
temperature
Operating:--10
"
C to 55
"
C (with no icing)
Storage:
--25
"
C to 65
"
C (with no icing)
Ambient
humidity
Operating: 35% to 85%
Humidity
class
DIN 40 040: G
PNP (Voltage) Input Models
Item
H3DR-AP
H3DR-ASP
H3DR-PP
Rated supply
voltage
100 to 240 VAC (50/60 Hz),
12 VDC,
24 VDC/VAC (50/60 Hz)
12 VDC,
24 VDC/VAC (50/60 Hz)
100 to 120 VAC (50/60 Hz),
200 to 240 VAC (50/60 Hz),
24 VDC/VAC (50/60 Hz)
Operating
voltage range
85% to 110% of rated supply voltage (90% to 110% with 12-VDC type)
Power reset
Minimum power-opening time: 0.1 s
Power
consumption
100 to 240 VAC: approx. 8 VA
12 VDC:
approx. 0.4 W
24 VDC/VAC:
approx. 1.3 VA (AC)
approx. 0.6 W (DC)
100 to 120 VAC: approx. 6 VA
200 to 240 VAC: approx. 10 VA
24 VDC/VAC:
approx. 2 VA (AC)
approx. 1 W (DC)
Control
outputs
Contacts: 5 A at 250 VAC, resistance
load (cos
%
= 1)
Transistor output: Open collector
(NPN/PNP),
100 mA max. at
30 VDC max.,
residual voltage:
2 V max.
Contacts: 5 A at 250 VAC, resistance
load (cos
%
= 1)
Ambient
temperature
Operating:--10
"
C to 55
"
C (with no icing)
Storage:
--25
"
C to 65
"
C (with no icing)
Ambient
humidity
Operating: 35% to 85%
Humidity
class
DIN 40 040: G