H3BA
H3BA
281
Specifications
Time Ranges
Time unit
s
min
hrs
10 h
Setting
0.5
0.05 to 0.5
0.05 to 0.5 h
1
0.1 to 1
1 to 10 h
5
0.5 to 5
5 to 50 h
10
1 to 10
10 to 100 h
Ratings
Rated supply voltage
24, 50, 100/110/120 or 200/220/240 VAC (50/60 Hz);
12, 24, 48, 100, or 110 VDC (permissible ripple: 20% max.)
Operating voltage range
All rated voltage except 12 VDC: 85% to 110% of rated supply voltage
12 VDC model: 90% to 110% of rated supply voltage
Power consumption
AC: approx. 10 VA/1 W; DC: approx. 1 W
Control outputs
5 A at 250 VAC, resistive load (cos
%
= 1)
Minimum permissible load (ref. value): 10 mA at 5 VDC, 100 mA at 5 VDC (-FA, -8H)
Characteristics
Accuracy of operating time
!
0.3% (see note 1)
Setting error
!
5%
Reset time
0.1 s max.
Influence of voltage
!
0.5% (see note 1)
Influence of temperature
!
2% max. (see note 1)
Insulation resistance
100 M
$
min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts and
between contact and control circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
Shock resistance
Destruction: 1,000 m/s
2
(approx. 100G)
Malfunction: 100 m/s
2
(approx. 10G)
Ambient temperature
Operating: --10
"
C to 55
"
C
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
See “Engineering Data.”
Approved standards
UL (File No. E41515), CSA (File No. LR22310), SEV (License No. D5.11/435)
Weight
H3BA, H3BA-8H, H3BA-8: approx. 100 g; H3BA-FA: approx. 170 g
Note:
When the timer is set at a rated time of 0.5 s or 1 s, add
!
10 ms to the respective characteristics.