H5CR
H5CR
184
Output mode d: Signal OFF delay (Timer resets when power comes on.)
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
The control output is energized at the
leading edge of the start signal.
Timing begins at the trailing edge of
the start signal. The control output is
de-energized when the present value
equals the preset time.
Output mode E: Interval (Timer resets when power comes on.)
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Timing begins on the leading edge of
the start signal. The control output is
only energized during timing. The
timer is reset when power is
interrupted or a reset signal is applied.
Output mode F: Cumulative (Timer does not reset when power comes on.)
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Timing begins on the leading edge of
the start signal. The control output is
energized when the cumulative
elapsed time of the start signal is
equal to the preset time. The output is
sustained until power is interrupted or
a reset signal applied.