H5L
H5L
253
Characteristics
Accuracy of operating time
!
0.01%
!
0.05 s max. (see note 1)
Setting error
Influence of voltage
Influence of temperature
Cyclic error
!
15 s (at 25
"
C)
Insulation resistance
100 M
$
min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed
non-current-carrying metal parts)
1,000 VAC, 50/60 Hz for 1 min (between control power supply circuit and contact control
output circuits, between non-continuous contacts)
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
Shock resistance
Destruction: 300 m/s
2
(approx. 30G)
Malfunction: 100 m/s
2
(approx. 10G)
Ambient temperature
Operating: --10
"
C to 55
"
C
Ambient humidity
Operating: 35% to 85%
Life expectancy
100,000 operations min. (15 A at 250 VAC, resistive load)
Approved standards
UL (File No. E52800), CSA (File No. LR22310), SEV
Weight
Approx. 350 g
Note:
The overall error, which includes repeat accuracy, setting error, and variations due to changes in voltage and temperature, is
!
0.01% or
!
0.05 s max..
Engineering Data
Ambient Operating Temperature and Carry Current
Note that the upper limit of the ambient operating temperature lowers
when a large carry current is being applies as shown below.
Upper
lim
it
of
am
bi
ent
te
m
perat
ure
(
C
)
"
Carry current AC/DC (A)