H5CL
H5CL
154
Operation
DIP Switch Setting
Pin no.
Item
OFF
ON
1, 2, 3
Time ranges
See table below.
4
Display modes
Up (Increment)
Down (Decrement)
5
Min. pulse width of inputs
20 ms
1 ms
6
Operating modes
A (signal ON-delay)
F (accumulative operation)
Note:
Set the DIP switch before installation and operation of the Unit. DIP switch setting changes are not effective while the power is on.
Time Ranges
1
2
3
Time range
ON
ON
ON
0.001 to 9.999 s
OFF
OFF
OFF
0.01 to 99.99 s
ON
OFF
OFF
0.1 to 999.9 s
OFF
ON
OFF
1 to 9999 s
ON
ON
OFF
0 min 01 s to 99 min 59 s
OFF
OFF
ON
0.1 to 999.9 min
ON
OFF
ON
0 h 01 min to 99 h 59 min
OFF
ON
ON
0.1 to 999.9 h
Note:
Switches 1 to 6 are all set to OFF before shipping.
(The same switch settings apply to AC and DC models)
ON
1
3 4 5 6
2
Top of Timer
Timer Control with Power Start
When using the H5CL with power start, short-circuit the start input and input 0-V terminals.
Operating Modes
A Mode
Signal ON-delay
F Mode
Accumulative Operation
Power
Start
Gate
Reset
Control output
Set value
0
0
Set value
Display
mode
Power
Start
Gate
Reset
Control output
Set value
0
0
Set value
Display
mode
UP
DOWN
UP
DOWN