H5CL
H5CL
157
Input Connections
Open Collector Output
Voltage Output
12 VDC
1
7
6
5
3
--
7
9
8
6
PC or sensor
0 V
Output
12 VDC
PC or sensor
0 V
Output
AC models
DC models
1
7
6
5
3
--
7
9
8
6
AC models
DC models
Gate
input
S
tart
input
R
e
set
input
12
V
D
C
o
utput
Gate
input
S
tart
input
R
e
set
input
12
V
D
C
o
utput
0V
0V
Contact input
7
6
5
3
7
9
8
6
AC models
DC models
Gate
input
S
tart
input
R
e
set
input
Start, Reset, and Gate Input Specification
ON impedance:
500
$
max. (the leakage current is 5 to 20 mA when the impedance is 0
$
.)
ON residual voltage:
2 V max.
OFF impedance:
100 k
$
min.
Maximum applicable voltage: 30 VDC max.
Two-wire Sensor
7
6
5
3
7
9
8
6
Sensor
0 V
AC models
DC models
Gate
input
S
tart
input
R
e
set
input
0V
Applicable Two-wire Sensor
Leakage current:
1.5 mA max.
Switching capacity: 5 mA min.
Residual voltage:
3 V max.
Operating voltage: 10 VDC
Note:
When connecting a two-wire sensor to a DC models, sup-
ply 24 VDC (21.6 to 26.4 VDC) to the timer.
Key Protection Input
4
3
10
6
AC models
DC models
Open collector
or
contact
0V
K
e
y
p
ro
tection
input
Key Protection Input
ON impedance:
1 k
$
max.
(the leakage current is approx. 1 mA when the impedance is 0
$
.)
ON residual voltage:
0.5 V max.
OFF impedance:
100 k
$
min.
Maximum applicable voltage: 30 VDC max.
Note:
The used contact should switch 1 mA at 5 V.
Precautions
Power Supplies
When turning the power ON and OFF, input signal reception is pos-
sible, unstable, or impossible as shown in the diagram below.
Power
supply
Input
Impossible
Unstable
Possible
Impossible
Unstable
160 ms
0 to 90ms
DC: 5 ms
AC: 10 ms
0 to 500 ms
ON
OFF
Apply the power supply voltage through a relay or switch in such a
way that the voltage reaches a fixed value immediately.
Turn the power ON and OFF with relay with a rated capacity of 10 A
minimum to prevent contact deterioration due to inrush current
caused by turning the power ON and OFF.