97
Error Procedures with Indicators
Section 9-1
Primary Errors That the Indicators Show and Error Procedures
Name
Color
Status
Primary error
Error procedure
MS
Green
Lit
Normal status
---
Red
Lit
Hardware fault in CompoNet
Communications Unit
Reset the Unit power supply.
If the problem stays, replace the CompoNet Communica-
tions Unit.
Flashing
Pin 1 (REGS) and pin 2 (I/O)
on the DIP switch are ON.
Turn OFF one of these pins and reset the Unit power sup-
ply.
The Registration Table data
is corrupt.
Make the registration table again.
The setting data for the
smart function is corrupt.
Write the correct parameters again with the CX-Integrator.
The backup data is corrupt.
Back up the data again.
Not lit
There is no Unit power sup-
ply.
Make sure that there is a Unit power supply.
NS
Green
Lit
Normal status
---
Flashing
The Unit is online but the
communications connection
is not completed. (The Com-
poNet Master Unit is com-
pleting the connection.)
• Make sure that you started the CompoNet Master Unit.
• Make sure that the SmartSlice I/O Terminal is in the
Registration Table in the CompoNet Master Unit.
Red
Lit
The same node address is
set for two or more nodes on
the CompoNet network.
Correct the node address settings and reset the Compo-
Net Communications Unit.
Communications stopped
because there are too many
communications errors.
Do a check of these items and then reset the CompoNet
Communications Unit.
• Make sure that the trunk line cables and branch line
cables are not too long.
• Make sure that the cables are not broken or loose.
• Make sure that terminating resistance connections are
correct.
• Make sure that the CompoNet Units and cables are not
near sources of noise.
Flashing
Communications timeout
Do a check of these items and then reset the CompoNet
Communications Unit.
• Make sure that the trunk line cables and branch line
cables are not too long.
• Make sure that the cables are not broken or loose.
• Make sure that terminating resistance connections are
correct.
• Make sure that the CompoNet Units and cables are not
near sources of noise.
Not lit
Node address duplication
check not complete
If only one CompoNet Communications Unit shows this
status, make sure that the connection of the communica-
tions cable is correct.
Summary of Contents for GRT1-CRT - 05-2008
Page 1: ...CompoNet Communications Unit Cat No W476 E1 01 SmartSlice GRT1 CRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 CRT CompoNet Communications Unit Operation Manual Produced May 2008 ...
Page 3: ...iv ...
Page 17: ...About this Manual xviii ...
Page 28: ...9 Specifications Section 1 4 1 4 3 Dimensions 12 23 1 25 1 61 2 69 7 58 3 8 4 3 mm ...
Page 29: ...10 Specifications Section 1 4 ...
Page 39: ...20 Switches Section 2 3 ...
Page 47: ...28 Installing the Turnback Units Section 3 2 ...
Page 99: ...80 Last Maintenance Date Section 6 12 ...
Page 113: ...94 Performance of Message Communications Section 8 2 ...
Page 127: ...108 Other Error Causes and Error Procedures Section 9 3 ...
Page 141: ...122 Power Consumption and Weight Tables Appendix D ...
Page 143: ...124 Total I O Current Consumption Table Appendix E ...
Page 147: ...128 Index ...
Page 149: ...130 Revision History ...