104
Error Procedures with CX-Integrator
Section 9-2
More Information on Errors in SmartSlice I/O Units
Error code
(hexadecimal
value)
Error description
“Detail”
Keeping error
history during
power
interruptions
Procedure
1st byte
2nd byte
0300
Reception error for backup
data
0x80:
SmartSlice
I/O
Node addresses
(hexadecimal
value)
Not kept
• Make sure that the
SmartSlice I/O Units are
correctly connected.
• Make sure that there
are no sources of noise
near the Unit.
0374
Transmission error
Cause
A transmission error
occurred.
0x80:
SmartSlice
I/O
Node addresses
(hexadecimal
value)
Not kept
• Make sure that the
SmartSlice I/O Units are
correctly connected.
• Make sure that there
are no sources of noise
near the Unit.
0375
Communications stopped
because of a transmission
error
Cause
A transmission error
occurred when the Unit
was set to stop communi-
cations for transmission
errors.
0x80:
SmartSlice
I/O
Node addresses
(hexadecimal
value)
Kept
• Make sure that the
SmartSlice I/O Units are
correctly connected.
• Make sure that there
are no sources of noise
near the Unit.
0376
Slave duplication error
Cause
A Slave duplication error
occurred.
0x80:
SmartSlice
I/O
Node addresses
(hexadecimal
value)
Not kept
Make sure that the
SmartSlice I/O Units are
connected correctly and
then reset the Compo-
Net Communications
Unit.
0378
I/O size error
0x00
0x00
Not kept
Make sure that the
SmartSlice I/O Units are
connected correctly and
then reset the Compo-
Net Communications
Unit.
0379
SmartSlice configuration
error
0x00
0x00
Not kept
Make sure that the
SmartSlice I/O Units are
connected correctly and
then reset the Compo-
Net Communications
Unit.
Summary of Contents for GRT1-CRT - 05-2008
Page 1: ...CompoNet Communications Unit Cat No W476 E1 01 SmartSlice GRT1 CRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 CRT CompoNet Communications Unit Operation Manual Produced May 2008 ...
Page 3: ...iv ...
Page 17: ...About this Manual xviii ...
Page 28: ...9 Specifications Section 1 4 1 4 3 Dimensions 12 23 1 25 1 61 2 69 7 58 3 8 4 3 mm ...
Page 29: ...10 Specifications Section 1 4 ...
Page 39: ...20 Switches Section 2 3 ...
Page 47: ...28 Installing the Turnback Units Section 3 2 ...
Page 99: ...80 Last Maintenance Date Section 6 12 ...
Page 113: ...94 Performance of Message Communications Section 8 2 ...
Page 127: ...108 Other Error Causes and Error Procedures Section 9 3 ...
Page 141: ...122 Power Consumption and Weight Tables Appendix D ...
Page 143: ...124 Total I O Current Consumption Table Appendix E ...
Page 147: ...128 Index ...
Page 149: ...130 Revision History ...