43
I/O Allocations to CompoNet Master Unit
Section 5-3
• The system allocates 2 bits to each Bit Unit starting from the lower bits.
Bit Units are SmartSlice I/O Units that have two or more bits of I/O (for
example, the GRT1-ID4/OD4).
• The system allocates words to each Word Unit starting from words
with lower addresses. Word Units are SmartSlice I/O Units that have
one or more words of I/O (for example, the GRT1-AD2/DA2C).
Refer to the
GRT1 Series SmartSlice I/O Units Operation Manual
(Cat. No.
W455) for information on each Bit Unit and Word Unit model of SmartSlice
I/O Units and specifications.
3.
Participation Status of the SmartSlice I/O Units
The system allocates 8 words for the participation status of the SmartSlice
I/O Units.
Allocation Example
The system allocates words to the SmartSlice I/O Units in the sequence in
which they are connected (in the sequence of unit numbers). The models of
the SmartSlice I/O Units have no effect on the sequence of allocations.
Unless you use the CX-Integrator to set I/O allocations, the system always
allocates words in the same sequence starting from the first word for the node
address. The sequence is the status, left SmartSlice I/O Unit, subsequent
SmartSlice I/O Unit on the right side, other SmartSlice I/O Units. The system
allocates words to Input Units in the Input Area and to Output Units in the Out-
put Area.
The system allocates words for status of the CompoNet Communications Unit
and the participation status of the SmartSlice I/O Units in the Input Area.
Data Patterns in I/O Memory
You can make these patterns in I/O memory for I/O allocations.
■
Input Area
• Input data + Status of CompoNet Communications Unit (default setting)
• Input data + Status of CompoNet Communications Unit + Participation
status of SmartSlice I/O Units
■
Output Area
• Output data only
You can use the CX-Integrator to select from these patterns.
+1
#3
#2
#1
#4
#6
#5
8
+2
+3
8
Slice I/O Units
Compo-
Net Com-
munica-
tions Unit
Unit 1
ID4
(4 bits)
Unit 2
ID4
(4 bits)
Unit 3
ID4
(4 bits)
Unit 4
AD2
(2 words)
Unit 5
OD4
(4 bits)
Unit 6
ROS2
(2 bits)
Word Bit 15
Input Area
Word
Bit 15
Bit 0
First
word
Status of CompoNet
Communications Unit
Not
used.
These bits are not allocated
because the subsequent Unit is a
Word Unit.
Output Area
Not
used.
Bit 0
First
word
Summary of Contents for GRT1-CRT - 05-2008
Page 1: ...CompoNet Communications Unit Cat No W476 E1 01 SmartSlice GRT1 CRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 CRT CompoNet Communications Unit Operation Manual Produced May 2008 ...
Page 3: ...iv ...
Page 17: ...About this Manual xviii ...
Page 28: ...9 Specifications Section 1 4 1 4 3 Dimensions 12 23 1 25 1 61 2 69 7 58 3 8 4 3 mm ...
Page 29: ...10 Specifications Section 1 4 ...
Page 39: ...20 Switches Section 2 3 ...
Page 47: ...28 Installing the Turnback Units Section 3 2 ...
Page 99: ...80 Last Maintenance Date Section 6 12 ...
Page 113: ...94 Performance of Message Communications Section 8 2 ...
Page 127: ...108 Other Error Causes and Error Procedures Section 9 3 ...
Page 141: ...122 Power Consumption and Weight Tables Appendix D ...
Page 143: ...124 Total I O Current Consumption Table Appendix E ...
Page 147: ...128 Index ...