8
Specifications
Section 1-4
Communications
media
You can use these cables:
Round Cable I (JIS C 3306, VCTF 2-core 0.75-mm
2
twisted-
pair cable)
Round Cable II (JIS C 3306, VCTF 4-core 0.75-mm
2
twisted-
pair cable)
Flat Cable I (without sheath, DCA4-4F10)
Flat Cable II (with sheath, DCA5-4F10)
Note
The Round Cable I, Round Cable II, Flat Cable I, and
Flat Cable II are different types of cable. You must use a
Repeater to divide a branch line from the main line to
use more than one type of cable.
Indicators
MS (green/red): This indicator shows the status of the Compo-
Net Communications Unit.
NS (green/red): This indicator shows the communications sta-
tus of the CompoNet network.
TS (green/red): This indicator shows the status of the Smart-
Slice I/O Terminal.
UNIT PWR (green): This indicator shows the status of the Unit
power supply.
I/O PWR (green): This indicator shows the status of the I/O
power supply.
Switches
Rotary switches: There are two rotary switches. You use them
to set the node address.
DIP switch: There is one DIP switch with four pins. You use
them to set the operating mode.
Connectors
There is one CompoNet communications connector.
Terminals
Clamp terminals for Unit power supply (24 VDC)
Clamp terminals for I/O power supply (24 VDC)
Power consumption
2.5 W
Power consumption
for each SmartSlice
I/O Terminal block
80 W max.
(You must divide the I/O Terminal into blocks to use more than
80 W.)
SmartSlice I/O Ter-
minal blocks
Main block and a maximum of two expansion blocks
Current consump-
tion for I/O power
supply
4 A max.
Weight 125
g
Accessories
None
Item
Specification
Summary of Contents for GRT1-CRT - 05-2008
Page 1: ...CompoNet Communications Unit Cat No W476 E1 01 SmartSlice GRT1 CRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 CRT CompoNet Communications Unit Operation Manual Produced May 2008 ...
Page 3: ...iv ...
Page 17: ...About this Manual xviii ...
Page 28: ...9 Specifications Section 1 4 1 4 3 Dimensions 12 23 1 25 1 61 2 69 7 58 3 8 4 3 mm ...
Page 29: ...10 Specifications Section 1 4 ...
Page 39: ...20 Switches Section 2 3 ...
Page 47: ...28 Installing the Turnback Units Section 3 2 ...
Page 99: ...80 Last Maintenance Date Section 6 12 ...
Page 113: ...94 Performance of Message Communications Section 8 2 ...
Page 127: ...108 Other Error Causes and Error Procedures Section 9 3 ...
Page 141: ...122 Power Consumption and Weight Tables Appendix D ...
Page 143: ...124 Total I O Current Consumption Table Appendix E ...
Page 147: ...128 Index ...
Page 149: ...130 Revision History ...