Specifications
This section tells you the specifications of the SmartSlice System and the
CompoNet Communications Unit.
1-4-1
Specifications of the SmartSlice System
General Specifications
SmartSlice Bus Communications Specifications
1-4-2
Specifications of the CompoNet Communications Unit
Item
Specification
Ambient operating
temperature
−
10 to 55
°
C (with no icing or condensation)
Ambient operating
humidity
25% to 85%
Ambient storage
temperature
−
25 to 65
°
C (with no icing or condensation)
Noise immunity
Complies with IEC 61000-4-4, 2.0 kV.
Vibration resistance
10 to 60 Hz: 0.7-mm double amplitude
60 to 150 Hz: 50 m/s
2
Withstand voltage
500 VAC (between isolated circuits)
Enclosure rating
IP20
Item
Specification
Types of communi-
cations
I/O communications and message communications
Turnback Cables
Length: 1 m, Maximum number of cables: 2
Connections
between Units in
SmartSlice I/O Ter-
minal
Building-block structure with slide connectors
Base block power
supply
Voltage: 24 VDC, Current: 4 A
Event messages
You can use event messages.
Item
Specification
Model GRT1-CRT
I/O points
Inputs: 32 bytes maximum (including status and areas which
the Unit does not use)
Output: 32 bytes maximum (including areas which the Unit
does not use)
Maximum number of
SmartSlice I/O Units
64 (Do not count the End Unit.)
Status area
1 word (This word shows the status of the CompoNet Commu-
nications Unit.)
Parameter backup
and restore
You can back up or restore a maximum of 2 KB of data for one
CompoNet Communications Unit.
Network power sup-
ply
14 to 26.4 VDC
I/O power supply
20.4 to 26.4 VDC
Baud rate
The CompoNet Communications Unit uses the baud rate of
the CompoNet Master Unit (93. 75 kbps, 1.5 Mbps, 3 Mbps, or
4 Mbps).
Summary of Contents for GRT1-CRT - 05-2008
Page 1: ...CompoNet Communications Unit Cat No W476 E1 01 SmartSlice GRT1 CRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 CRT CompoNet Communications Unit Operation Manual Produced May 2008 ...
Page 3: ...iv ...
Page 17: ...About this Manual xviii ...
Page 28: ...9 Specifications Section 1 4 1 4 3 Dimensions 12 23 1 25 1 61 2 69 7 58 3 8 4 3 mm ...
Page 29: ...10 Specifications Section 1 4 ...
Page 39: ...20 Switches Section 2 3 ...
Page 47: ...28 Installing the Turnback Units Section 3 2 ...
Page 99: ...80 Last Maintenance Date Section 6 12 ...
Page 113: ...94 Performance of Message Communications Section 8 2 ...
Page 127: ...108 Other Error Causes and Error Procedures Section 9 3 ...
Page 141: ...122 Power Consumption and Weight Tables Appendix D ...
Page 143: ...124 Total I O Current Consumption Table Appendix E ...
Page 147: ...128 Index ...
Page 149: ...130 Revision History ...