18
Switches
Section 2-3
2-3
Switches
This section tells you the functions of the rotary switches and the DIP switch
on the front panel of the CompoNet Communications Unit.
2-3-1
Rotary Switches
Use the rotary switches to set the node address of the CompoNet Communi-
cations Unit as a slave on the CompoNet network. Set the node address as a
decimal number between 0 and 63.
Set the 10s digit on the left rotary switch and set the 1s digit on the right rotary
switch.
The setting of the switches is read when the Unit power supply turns ON.
2-3-2
DIP Switch
Use the DIP switch to create the registration table, set the I/O allocation
mode, back up SmartSlice I/O Unit parameters, and restore the SmartSlice
I/O Unit parameters.
Note
All pins on the DIP switch are OFF in the factory settings.
Pin 1: REGS
Use pin 1 to make or change the Registration Table. The setting of pin 1 when
the Unit power supply turns ON enables or disables the Registration Table.
While the Unit power supply is ON, turn ON pin 1 to make the registration
table.
• The Pin Setting When the Unit Power Supply Turns ON
• Changing the Pin Setting While the Unit Power Supply Is ON
Note
The setting of pin 1 is enabled when pin 2 (I/O) is OFF (Automatic I/O Alloca-
tion Mode).
×
10
×
1
ON
1
2
3
4
REGS
I/O
ADR
BACK
Pin setting
Description
ON
If there is no Registration Table, the CompoNet Communications Unit
will record the connected SmartSlice I/O Units in a table. The table
tells the sequence and I/O capacity of each SmartSlice I/O Unit. If
there is a Registration Table, the CompoNet Communications Unit will
automatically compare the connected SmartSlice I/O Units with the
Registration Table. If the connected SmartSlice I/O Units do not agree
with the Registration Table, communications will not start for all
SmartSlice I/O Units.
OFF
The CompoNet Communications Unit will disable the Registration
Table and will do communications with all SmartSlice I/O Units.
Pin setting
Description
OFF to ON
The CompoNet Communications Unit makes the Registration Table.
Summary of Contents for GRT1-CRT - 05-2008
Page 1: ...CompoNet Communications Unit Cat No W476 E1 01 SmartSlice GRT1 CRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 CRT CompoNet Communications Unit Operation Manual Produced May 2008 ...
Page 3: ...iv ...
Page 17: ...About this Manual xviii ...
Page 28: ...9 Specifications Section 1 4 1 4 3 Dimensions 12 23 1 25 1 61 2 69 7 58 3 8 4 3 mm ...
Page 29: ...10 Specifications Section 1 4 ...
Page 39: ...20 Switches Section 2 3 ...
Page 47: ...28 Installing the Turnback Units Section 3 2 ...
Page 99: ...80 Last Maintenance Date Section 6 12 ...
Page 113: ...94 Performance of Message Communications Section 8 2 ...
Page 127: ...108 Other Error Causes and Error Procedures Section 9 3 ...
Page 141: ...122 Power Consumption and Weight Tables Appendix D ...
Page 143: ...124 Total I O Current Consumption Table Appendix E ...
Page 147: ...128 Index ...
Page 149: ...130 Revision History ...