98
Error Procedures with Indicators
Section 9-1
TS
Green
Lit
Normal status
---
Flashing
The total I/O size of the
SmartSlice I/O Units is larger
than the specification.
Make the configuration smaller. The I/O size must be no
larger than 32 input bytes and 32 output bytes. Then reset
the CompoNet Communications Unit.
Backing up parameters
Let the backup operation continue until it is completed.
Restoring parameters
Let the restore operation continue until it is completed.
Doing process to join the
network
Let the join process continue until it is completed.
The process to join the net-
work was not completed cor-
rectly.
Make sure that you connected the End Unit correctly and
then reset the CompoNet Communications Unit.
Red
Lit
Configuration error for
SmartSlice I/O Units
Do a check of these items.
• Make sure that there are no more than 64 SmartSlice I/O
Units.
• Make sure that the I/O size is no larger than 32 input
bytes and 32 output bytes.
Lit for 2 s
Backup operation failure
Back up the data again.
Restore operation failure
Make sure that the SmartSlice I/O Units are installed cor-
rectly and reset the CompoNet Communications Unit.
Pin 1 (REGS) of the DIP
switch turned ON in Soft-
ware I/O Allocation Mode.
Turn OFF pin 1 and then reset the CompoNet Communi-
cations Unit.
Flashing
Communications error on
SmartSlice bus
Make sure that the Base Blocks are correctly connected in
the SmartSlice I/O Terminal.
The Registration Table is
enabled, but it does not
agree with the I/O configura-
tion.
Do a check of the I/O configuration and reset the Compo-
Net Communications Unit.
In Software I/O Allocation
Mode, an I/O Unit that is set
to “Mount” in the Software
Setting Table is missing.
Make sure that the correct SmartSlice I/O Unit is installed
or remove the “Mount” setting and then reset the Compo-
Net Communications Unit.
Not lit
There is no Unit power sup-
ply.
Make sure that the CompoNet Communications Unit has
a Unit power supply.
UNIT
PWR
Green
Lit
Normal status
---
Not lit
There is no Unit power sup-
ply.
Make sure that the CompoNet Communications Unit has
a Unit power supply with sufficient capacity for the Smart-
Slice I/O Terminal.
I/O PWR
Green
Lit
Normal status
---
Not lit
There is no I/O power sup-
ply.
Make sure that the CompoNet Communications Unit has
an I/O power supply with sufficient capacity for the Smart-
Slice I/O Units and connected sensors and actuators.
Name
Color
Status
Primary error
Error procedure
Summary of Contents for GRT1-CRT - 05-2008
Page 1: ...CompoNet Communications Unit Cat No W476 E1 01 SmartSlice GRT1 CRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 CRT CompoNet Communications Unit Operation Manual Produced May 2008 ...
Page 3: ...iv ...
Page 17: ...About this Manual xviii ...
Page 28: ...9 Specifications Section 1 4 1 4 3 Dimensions 12 23 1 25 1 61 2 69 7 58 3 8 4 3 mm ...
Page 29: ...10 Specifications Section 1 4 ...
Page 39: ...20 Switches Section 2 3 ...
Page 47: ...28 Installing the Turnback Units Section 3 2 ...
Page 99: ...80 Last Maintenance Date Section 6 12 ...
Page 113: ...94 Performance of Message Communications Section 8 2 ...
Page 127: ...108 Other Error Causes and Error Procedures Section 9 3 ...
Page 141: ...122 Power Consumption and Weight Tables Appendix D ...
Page 143: ...124 Total I O Current Consumption Table Appendix E ...
Page 147: ...128 Index ...
Page 149: ...130 Revision History ...