58
Automatic Restore Function
Section 6-4
(2) The CompoNet Communications Unit will clear the backup data if you
change the operating mode.
The CompoNet Communications Unit will clear the backup data if you
back up the parameters with pin 2 (I/O) ON (Software I/O Allocation
Mode) and then make the Registration Table from the CX-Integrator.
6-4
Automatic Restore Function
After you replace a SmartSlice I/O Unit, you can use the Automatic Restore
Function to automatically download the parameters in the CompoNet Com-
munications Unit to the SmartSlice I/O Units.
These conditions are necessary to automatically restore the parameters. Do a
check of these conditions before you restore the parameters.
• There must be backup data in the CompoNet Communications Unit.
• Pin 1 (REGS) or pin 2 (I/O) on the DIP switch on the CompoNet Commu-
nications Unit must be ON.
• The new SmartSlice I/O Unit must have the same unit number and model
number as the previous SmartSlice I/O Unit, but a different serial number.
6-4-1
Restore Procedure
1,2,3...
1.
Turn ON pin 3 (ADR) on the CompoNet Communications Unit to enable the
Automatic Restore Function.
2.
Turn OFF the I/O power supply and replace the SmartSlice I/O Unit.
Refer to the
GRT1 Series SmartSlice I/O Units Operation Manual
(Cat. No.
W455) for information on how to replace SmartSlice I/O Units.
The CompoNet Communications Unit will detect the SmartSlice I/O Unit that
you replaced and it will download the parameters to it.
!WARNING
Turn OFF the I/O power supply to a SmartSlice I/O Unit before you replace it.
Incorrect inputs, incorrect outputs, or electrical shock can occur if you do not
turn OFF the I/O power supply. If there is external power to a terminal for a
Relay Output Slave, for example, turn OFF the external power before you
replace the SmartSlice I/O Unit.
3.
Turn ON the I/O power supply.
#1
#2
#4
#3
Power ON
CompoNet
Communica-
tions Unit
Turn ON pin 3 when
pin 1 or pin 2 is ON.
Parameters
The CompoNet Communications
Unit will automatically download
the parameters to the new Unit.
• Do not turn OFF the power supply or reset the CompoNet Communications
Unit from the CX-Integrator during the restore operation. The restored data
will not be correct.
Precaution for
Correct Usage
Summary of Contents for GRT1-CRT - 05-2008
Page 1: ...CompoNet Communications Unit Cat No W476 E1 01 SmartSlice GRT1 CRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 CRT CompoNet Communications Unit Operation Manual Produced May 2008 ...
Page 3: ...iv ...
Page 17: ...About this Manual xviii ...
Page 28: ...9 Specifications Section 1 4 1 4 3 Dimensions 12 23 1 25 1 61 2 69 7 58 3 8 4 3 mm ...
Page 29: ...10 Specifications Section 1 4 ...
Page 39: ...20 Switches Section 2 3 ...
Page 47: ...28 Installing the Turnback Units Section 3 2 ...
Page 99: ...80 Last Maintenance Date Section 6 12 ...
Page 113: ...94 Performance of Message Communications Section 8 2 ...
Page 127: ...108 Other Error Causes and Error Procedures Section 9 3 ...
Page 141: ...122 Power Consumption and Weight Tables Appendix D ...
Page 143: ...124 Total I O Current Consumption Table Appendix E ...
Page 147: ...128 Index ...
Page 149: ...130 Revision History ...