Description of FINS Commands
Section
6-3
185
Note 2
Specify the parameter type, write start address, data length and write data for
the number of ITEMs.
Response format
Command code
Response code
Data format
02 Hex
43 Hex
MRES
SRES
Data length
(bytes)
1
1
1
1
When all ITEMs to be written can be written, and all ITEMs have been written
successfully, this shall be regarded as a normal completion.
Response code
Response code
Meaning
0000 Hex
Normal completion
1001 Hex
Command length over
The command length exceeds 2002 bytes.
1002 Hex
Insufficient command length
The command length is less than four bytes.
1003 Hex
Number of elements/number of data mismatch
The number of data items does not match the number of
ITEMs.
1101 Hex
No type
An unusable block address was specified in the parameter
type.
The block address specified in the parameter type is an
unregistered function block.
Function blocks other than System Common blocks cannot be
accessed as the RAM has not yet been initialized (cleared)
after a battery failure causes content of RAM to be lost.
1103 Hex
Specified address out-of-range error
The start address contains a non-existent ITEM.
An attempt was made to write to the format setting of a
System Common block.
110C Hex
Other item parameter error
Number of ITEMs is 0.
The specified data length does not match the actual data of
each ITEM specified by the write start address.
The combination of block address and block format is
forbidden.
Write data is out of the data range for each ITEM.