Exchanging Data with CX-Process Monitor/SCADA Software and with Other Nodes
Section
3-4
131
CPU Unit
Words specified
in Receive All
Blocks
Words specified
in Send All
Blocks
Loop Control Unit
Expanded CPU
Unit Terminal
Send All
Blocks
I/O memory
SCADA software
Specify CSV
tags and read
Specify CSV tags
and write
Control Block
ITEMs
Operation
Block ITEMs
External
Controller
Terminal
ITEMs
Every
execution
cycle
Receive All
Blocks
Specified words
Specified words
Specify CSV tags and
read
Specify CSV tags and
write
Note
CSV tags are used by SCADA software. The CSV tags consist of tag
numbers set for each function block, tag ITEMs corresponding to the function
block ITEMs, and the I/O memory address for each ITEM in the CPU Unit.
CSV tags are created using the CX-Process Tool. A CSV tag file can be
imported to an OPC server, tag numbers and tag ITEMS can be specified
from RS View or other SCADA software on the OPC server, and then the
data can be written to the Loop Control Unit.
Create (compile after settingCSV tags)
Tag No.
TIC001
PV
Tag No. (representative tags)
LCU001
TIC001
PV
3
200
LCU001
TIC001
SP
3
201
LCU001
TIC005
PV
3
300
Address in I/O memory in CPU Unit
Example: D00200 (area is specified as 3 for DM)
I/O memory area in CPU Unit
Example: 3 (DM area)
Example:
CSV tags
SCADA software
Tag ITEM