Examples of Applied Control Types
Section
5-2
172
Example
PID
MV
PV
Air
Rotary drier
Moisture meter
Analog
output
Analog
input
021
007
Dead Time Compensation
<Block Model 149>
014
006
Advanced PID
<Block Model 012>
Address 001
087
MV
PV compensation sw itch
PV
021
046
047
045
PV compensation mode: "Add"
PV compensation input
Address 101
Block address
ITEM
No.
Data
Explanation
002
586
AI 4-point Terminal block
901
021
Y1 (analog input 1)
002
587
AO 4-point Terminal block
021
001087
X1 (analog output 1) source designation
902
031
X1 (analog output 1)
002
012
Advanced PID block
006
901021
PV source designation
045
1
PV compensation system (add)
046
PV compensation switch
047
100014
PV compensation input source designation
001
087
MV
002
149
Dead Time Compensation block
007
001087
X1 source designation
009
K (gain) 0 to 10.000
010
T (lead time constant) 0 to 999.9 s
011
H (sampling cycle) 0 to 9999 s
012
N (number of samples) 0 to 20
100
014
Y1 output value