Description of FINS Commands
Section
6-3
183
Note 3
For details of the data length of each ITEM, refer to the rightmost column
"Data length (bytes)" in the ITEM Lists in Section 2 Description of Function
Blocks in the Function Block Reference Manual.
Response code
Response code
Meaning
0000 Hex
Normal completion
1001 Hex
Command length over
The command length exceeds 2002 bytes.
1002 Hex
Insufficient command length
The command length is less than four bytes.
1003 Hex
Number of elements/number of data mismatch
The number of read start addresses does not match the
number of ITEMs.
1101 Hex
No type
An unusable block address was specified in the parameter
type.
The block address specified in the parameter type is an
unregistered function block.
Function blocks other than System Common blocks cannot be
accessed as the RAM has not yet been initialized (cleared)
after a battery failure causes content of RAM to be lost.
1103 Hex
Specified address out-of-range error
There is not even one ITEM specified by the start address.
110B Hex
Response exceeds maximum response length
The length of the read data section exceeds 968 bytes.
110C Hex
Other item parameter error
Number of ITEMs is 0.