Simple Example of Use
Section
4-1
140
4-1 Simple Example of Use
This section describes the basic procedure for using the Loop Control Unit for
cascade control.
Step 1
Design
1, 2, 3…
1. Prepare an instrumentation drawing.
PID2
PV 1
MV 1
PID1
MV 2
PV 2
0.0 to 400.0 m
3
/HR
0.0 to 300.0
°
C
2. Decide on the PC system configuration.
CPU Unit
Loop Control Unit
Analog Output Unit
Temperature
converter
4 to 20 mA
Differential pressure
transmitter
4 to 20 mA
4 to 20 mA
Control valve
Analog Input Unit
Product name
Model
Description
CPU Unit
CS1H/G-
CPU
Loop Control Unit
CS1W-LC001
Analog Input Unit
CS1W-AD041
Analog input 1:
4 to 20 mA (temperature conversion
input)
Analog input 2:
4 to 20 mA (differential pressure
transmitter input)
Analog Output Unit
CS1W-DA041
Analog output 1:
4 to 20 mA (output to control valve)