230
Data Link table of PC#1
A total of 636 words (S to S+635 words) comprising system information (24 words), Area to send to
computer (512 words) and Area to send to all nodes (100 words) are sent to the computer.
The uppermost 100 words (T+436 to T+535 words) of the Area to send to computer of PC#2 are received at
the Area to send to all nodes (S+636 to S+735 words) of the self node number (#1) as dummy words.
The 100 words (T+536 to T+635 words) of the Area to send to all nodes of PC#2 are received at the Area to
send to all nodes (S+736 to +835 words) of node number (#2).
Data Link table of PC#2
A total of 636 words (T to T+635 words) comprising system information (24 words), Area to send to
computer (512 words) and Area to send to all nodes (100 words) are sent to the computer.
The 100 words (S+536 to S+635 words) of the Area to send to all nodes of PC#1 are received at the Area to
receive from all nodes (T+636 to T+735 words) of the self node number (#2).
Data Link table of PC#32
The system information (24 words) from PC#1 and PC#2, Area to send to computer (512 words) and Area to
send to all nodes (100 words) are each received in node number order.