Names and Functions of Parts
Section
2-1
61
LED Indicators
RUN
LC001
RD
SD
ERC
ERH
CS
Indication
Name
Color
State
Description
Out
System stopped
A probable cause is one of the following:
Initialization of unit in progress
Unit hardware trouble
No power supply from power supply unit
Unit WDT error
Operation of Loop Control Unit stopped
(A probable cause is one of the following:)
- Regular operation stopped
- CPU Unit operation stop error
- CPU Unit in standby mode
- Load rate exceeded at operation cycle of 2 s
(Operation Cycle Automatic Switching
Generation flag ON)
RUN
CPU Unit
running
Green
Lit
Loop Control Unit running
Out
No CPU Unit error
ERH
CPU Unit
error
Red
Lit
CPU Unit error
Out
No error
Lit
Error
ERC
Loop
Control
Unit error
Red
Blinking Battery error (only when pin 2 of DIP switch is OFF)
SD
Not used
RD
Not used
Battery
When the battery compartment cover is opened, you can access the battery
mounted as shown below.
Battery
2
1
ON
The battery is used for backing up the following data in the Loop Control Unit:
Function block data
Error log data
If pin 2 of the DIP switch is OFF and the battery voltage drops or a battery is
not mounted, the ERC LED on the front panel blinks. At the same time, bit 05
of the leading n words of the allocated relay area and ITEM095 of the System
Common block (Block Model 000) become 1 (ON), and the error log code
(0330 for battery error and 0331 for function block database error) is stored
on the Loop Control Unit.
Note
If pin 2 of the DIP switch is ON, flash memory contents will be automatically
transferred to RAM at startup, bit 5 of word n will be ON, and ITEM 095 of the