Description of FINS Commands
Section
6-3
186
command code
READ LOOP CONTROL UNIT INFORMATION
05 01
Function
Reads the model number and version information of the Loop Control Unit.
Command format
Command code
Data format
05 Hex
01 Hex
Data length
(bytes)
1
1
Response format
Command code
Response code
Data format
05 Hex
01 Hex
MRES
SRES
Block Model
Version
Data length
(bytes)
1
1
1
1
20
20
1) Model number
The format comprising up to 20 ASCII code characters beginning from the
left is returned. The model number is filled with spaces (20 Hex) from the
right if less than 20 characters.
The model number of the Loop Control Unit is "CS1W-LC001."
2) Version
The version of the system program comprising up to 20 ASCII code
characters beginning from the left is returned. The model number is filled
with spaces (20 Hex) from the right if less than 20 characters.
The version returned looks as if it has two versions "V1.00V1.00". The
former version is the version of the system program stored in MPU built-in
ROM, and the latter is the version stored in flash ROM.
Response code
Response code
Meaning
0000 Hex
Normal completion
1001 Hex
Command length over
The command length exceeds two bytes.