How to Use the Node Terminal Block
Appendix 2
226
Actual example
The following shows a simple example.
PV1
AI 4-point
Terminal Block
Model 586
Basic PID Block
Model 011
Basic PID Block
Model 011
MV1
PV2
RSP
MV2
AO 4-point
Terminal Block
Model 587
PID1
PID2
In the above example, basic PID is specified as follows on the 1-Block Send Terminal to Computer (Block
Model 403) as the source designation function block address.
Block address ITEM No.
Data
Explanation
002
403
1-Block Send Terminal to Computer
501
011
001
PID1 of block address 001 is sent to CX-Process Monitor
running on the computer.
002
403
1-Block Send Terminal to Computer
502
011
002
PID2 of block address 002 is sent to CX-Process Monitor
running on the computer.
001
002
011
Basic PID (PID1)
002
002
011
Basic PID (PID2)
PV1
AI 4-point
Terminal
Block Model
586
Basic PID Block
Model 011
Basic PID Block
Model 011
MV1
PV2
RSP
MV2
AO 4-point
Terminal
Block Model
587
1-Block Send Terminal to Computer
Block Model 403
1-Block Send Terminal to Computer
Block Model 403
Area to send to
computer in Data
Memory (D) for
Node Terminal
CPU Unit’s I/O memory, Data
Memory (D) area
Send
command
Send
command
Send
Send