Description of Operation
Section
3-2
111
1) Analog values are written on the allocated CIO area of the analog output
data on the Analog Output Unit and Analog Input/Output Unit.
2) Writing is performed internally on the leading words (n) of the allocated
CIO area on the Analog Output Unit and Analog Input/Output Unit.
For this reason, if the wrong unit number on the Field Terminals is set,
the wrong data will be written to the allocated CIO area of the Special I/O
Unit having that unit number, and may cause the overall PC system to
malfunction.
Before starting running of the Loop Control Unit, first make sure that the
unit number on the Field Terminals matches that set on the front panel of
the Analog Input/Output Unit.
Field Terminals that undergo writing by the Loop Control Unit
Model
Function
block name
Target Analog
Input/Output
Unit
Internal writing by
Loop Control Unit
Writing of
analog values
552
AO 8-point
Terminal
(DA003/4)
C200H-
DA003/004
00FF Hex is stored
to leading allocated
word (n).
Analog value is
stored to
allocated area
n+1 to n+8.
553
AI 2-point/Ao
2-point
Terminal
(MAD01)
C200H-
MAD01
0003 Hex is stored
to leading allocated
word (n).
Analog value is
stored to
allocated area
n+1 to n+2.
583
AI 4-point/Ao
4-point
Terminal
(MAD44)
CS1W-
MAD44
000F Hex is stored
to leading allocated
word (n).
Analog value is
stored to
allocated area
n+1 to n+4.
563
AO 4-point
Terminal
(PMV01)
CS1W-
PMV01
(isolated-type
control output)
None
Analog value is
stored to
allocated area
n+1 to n+4.
585
AO 8-point
Terminal
(DA08V/C)
CS1W-
DA08V/C
00FF Hex is stored
to leading allocated
word (n).
Analog value is
stored to
allocated area
n+1 to n+8.
587
AO 4-point
Terminal
(DA041)
CS1W-DA041
000F Hex is stored
to leading allocated
word (n).
Analog value is
stored to
allocated area
n+1 to n+4.