How to Use the Node Terminal Block
Appendix 2
224
How to Set Controller Link Data Link Tables
When the Node Terminal block is used to send and receive data to and from the personal computer on the
Controller Link or a Loop Control Unit at another PC, the Controller Link Data Link (user setting) table (Note)
shown below must be prepared and registered (downloaded) on each node.
Note
A "Data Link table" specifies which area on the self node is to be sent and how many words are to be
received from which area on other nodes.
There are two modes of connection, connection modes 1 and 2. The connection mode is determined by
whether the connection is with only the computer on which CX-Process Monitor is running, or the connection
is also with the Loop Control Unit at another node PC.
Connection mode 1: Connection with only the computer on which CX-Process Monitor is running
Connection mode 2: Connection with the Loop Control Unit at another node PC and the computer on which
CX-Process Monitor is running
Connection mode 1) Connection with only the computer on which CX-Process
Monitor is running
Data Link table settings
Item
Description
Type of data link
Any setting
Link start word
Same as leading address (S) of Data Memory (on CPU
Unit) for the Node Terminals
Self node leading send word
Same as leading address (S) of Data Memory (on CPU
Unit) for the Node Terminals
Number of self node send words
536 words
Description of above settings
Area
Send/
Receive
Number of
words
Description
24 words of system information
Send to computer on which
CX-Process Monitor is running
512 words of Area to send to
computer
Send
536 words
Send to computer on which
CX-Process Monitor is running
The following shows an example of how to set the Data Link table.