How to Use the Node Terminal Block
Appendix 2
227
Block addresses 501 and 502 are each sent (allocated) to the Area to send to computer of the Data Memory
area for the node terminals.
When the leading address (S) of the Data Memory area for the Node Terminals is taken to be D16020 (set to
ITEM043):
Data Memory (D) for Node Terminals
15
00
S
D16020
S+1
D16021
~
~
S+23
D16043
System information
S+24
D16044
~
~
S+39
D16059
Terminal to computer send block at block
number 501 (PID1 of basic PID)
S+40
D16060
~
~
S+55
D16075
Terminal to computer send block at block
number 502 (PID2 of basic PID)
S+56
D16076
~
~
S+535
D16555
Not allocated (Note, however, that transmission
to computer is required for Controller Link Data
Link.)
In this example, let’s assume that the PC is node 01 and that the computer on which CX-Process Monitor is
running is node 02.
Each of the data link tables is set as follows:
Node: 01, Link start word: D16020
Node
Send/
Receive
Leading
word of
self node
Number of
words
Offset
01
Send
D16020
536 words
02
Reception
OFF
Node: 02, Link start word: P
Node
Send/
Receive
Leading
word of
self node
Number of
words
Offset
01
Receive
P
536 words
0 word
02
Send OFF
Data Memory (D) for PC Node Terminals
Computer on which CX-Process Monitor is
running
15
00
S
D16020
P
S+1
D16021
~
~
S+23
D16043
System information
System information
S+24
D16044
Send by Controller Link Data Link
~
~
S+39
D16059
Terminal to computer send block at block number
501 (PID1 of basic PID)
Terminal to computer send block at block number
501 (PID1 of basic PID)
S+40
D16060
~
~
S+55
D16075
Terminal to computer send block at block number
502 (PID2 of basic PID)
Terminal to computer send block at block number
502 (PID2 of basic PID)
S+56
D16076
~
~
S+535
D16555
Not allocated (Note, however, that transmission
to computer is required for Controller Link Data
Link.)