Errors and Alarm Troubleshooting
Section
7-1
193
Errors that occur during initial processing (at CPU Unit power ON or restart of the Loop Control Unit)
LED
RUN
ERH
ERC
Item
Cause
State
Error code
(stored as
error log data)
Remedy
1) The same unit
number has been
specified twice or
more on the same
CPU Unit.
None
1) Set the correct unit
number, and turn the
power back ON again.
2) The unit number is
not registered to CPU
Unit I/O table.
0006 detailed
code: 0800
2) Prepare an I/O table.
3) Failed to recognize
the CPU Unit
None
3) Replace the Loop
Control Unit if ERH lights
even if mounted on a
different CPU Unit.
Out
Lit
Out
Unit
number
setting
error
4) Error occurred during
initial processing on
CPU Unit.
All functions
stopped
000F
4) Refer to the CPU Unit
Operation Manual.
Out
Lit
Lit
Initial
recognition
error
Failed to recognize the
CPU Unit
All functions
stopped
None
Replace the Loop Control
Unit if ERH/ERC light even
if mounted on a different
CPU Unit.
Out
Out
Lit
Unit error
Hardware malfunction
such as memory
malfunction was
detected during the self-
diagnostic test.
All functions
stopped
None
Replace the Loop Control
Unit if ERC lights even if
mounted on a different
CPU Unit.
1) The correct internal
power is not being
supplied to the Loop
Control Unit.
1) Check the power
voltage, and supply the
correct power. Or, check
the total current
consumption of the PC.
2) The unit is not
properly fixed to the
Backplane.
2) Firmly fix the Loop
Control Unit on the
Backplane.
Out
Out
Out
Power
supply
failure
3) The unit is
malfunctioning.
All functions
stopped
None
3) Replace the Loop
Control Unit if LED goes
off even if mounted on a
different CPU Unit.
1) Drop in internal
battery power voltage
or battery not
mounted (Only when
DIP switch pin 2 is
OFF)
All functions
stopped
Running
stopped
1) Check the battery
connection. If the
connection is normal,
replace the battery.
Then execute
initialization using CX-
Process Tool.
(not
related)
(not
related)
Lit
Function
block
database
error
2) Data corruption
caused by noise
In the case of
only a partial
error, running
is stopped
only at the
function block
in question.
0331
Detailed code:
Block
address.
FFFF
indicates that
the entire
database is in
error.
2) Set the data again to
the function block in
question using CX-
Process Tool.