background image

 

 

WISE-5801 SMS 

Application Example 

 

Scenario

 

The  following  scenario  assume  using  WISE-5801  controller  in  a  greenhouse 
environment monitoring application. The WISE-5801 is connected to an I-7019R 
and an I-7061D remote I/O modules. The AI channel 0 on I-7019R will read the 
room  temperature  and  the  DO  channel  0  and  1  on  I-7061D  are  connected 
separately to the air conditioning equipment and sprinkler. The DO channel 2 on 
I-7061D is connected to the lighting system to prolong the sun exposure. When 
the  room  temperature  is  higher  than  40°C,  the  WISE-5801  will  send  a  SMS 
message with the real-time temperature value to the operator. The operator could 
turn on/off the air conditioner and sprinkler via SMS command. In addition, the 
operator could also review the number of time the air conditioner and sprinkler 
being turned on and control the lighting in real-time.   
 

 

 

Summary of Contents for WISE-5801

Page 1: ...onnected separately to the air conditioning equipment and sprinkler The DO channel 2 on I 7061D is connected to the lighting system to prolong the sun exposure When the room temperature is higher than...

Page 2: ...ge as follow to the operator SMS Command 1 set as 1 To turn off the air conditioner and the sprinkler the operator could send back a SMS command to the WISE 5801 like this ACT 1 0 or using SMS Quick c...

Page 3: ...off the lighting of the room SET m2do2 0 or using SMS Quick command light 0 After the WISE 5801 receives the command it will return a SMS message as follow to the operator SET I 7061 2 DO Channel 2 as...

Page 4: ...he Setting button on the module list as indicated to edit the settings for detailed module settings information please refer to the user manual 4 On the I 7019 Module Setting page in the AI Attribute...

Page 5: ...5 On the I 7000 Module Setting Page continue to add I 7061D module to the list in this case the I 7061D locates at address 2...

Page 6: ...s are accurate click Save button to save the module settings 7 Click on 2 Advanced Setting to get into the Advanced Setting page 8 On the Advanced Setting page click on Internal Register Setting to ge...

Page 7: ...On the Internal Register Setting page check the box of No 01 to enable the Internal Register No 01 and click Save button 10 On the Advanced Setting page click on SMS Setting to get into the setting pa...

Page 8: ...o be input in the format Country code area code and number In this case you are required to input the cell phone number 0987654321 in Taiwan area therefore please input the Authorized Phone Number as...

Page 9: ...mand field Select Internal Register and 1 in the Module field then press Insert button to insert the command string to the original command field You can also directly input the command string ir1 in...

Page 10: ...umber of SMS alarm messages to be 1 from the dropdown list ii In the Index field specify the SMS index number to be 1 from the dropdown list iii In the Phone Number field input the phone numbers to re...

Page 11: ...20 Make sure all settings are accurate click Save button to save the changes...

Page 12: ...g Page on the right side select AI as IF Condition for Condition 1 and then click on the right side button to get into the AI Condition Setting page 24 In the Module Channel section select I 7019 1 an...

Page 13: ...ield as indicated to get into the SMS Alarm Action Setting page 26 In the Index field select 1 and verify the SMS information Click Save button to save the settings and return to the Rule1 Setting Pag...

Page 14: ...e right side select SMS Command as IF Condition for Condition 1 and then click on the right side button to get into the SMS Command Condition Setting page 30 In the Index field select 1 and in the Val...

Page 15: ...le Channel section select I 7061 2 and channel 0 from the dropdown list In the Channel Value section select ON from the dropdown list Then click Save button to save the settings and return to the Rule...

Page 16: ...elect ON from the dropdown list Then click Save button to save the settings and return to the Rule2 Setting Page 35 In the THEN section in the Action3 field select Internal Register from the dropdown...

Page 17: ...2 Setting Page 37 In the ELSE section in the Action1 field select DO from the dropdown list click the button next to the Action 1 field as indicated to get into the DO Action Setting page 38 In the Mo...

Page 18: ...o the DO Action Setting page 40 In the Module Channel section select I 7061 2 and channel 1 from the dropdown list In the Channel Value section select OFF from the dropdown list Then click Save button...

Page 19: ...inish the rule editing click the Download to Module button to download the rule setting 43 After the download process is completed click Reboot button to make the new updated settings take effect Rule...

Page 20: ......