Basic Examples of PID Control
Section
5-1
158
5-1-5
Ramp Program Control
Follow the procedure below to perform program control for changing the Set
Point value in a ramp manner proportionately to the elapsed time.
Function blocks used: Basic PID (Block Model 011)
Ramp Program (Block Model 155)
Step Ladder Program (Block Model 301)
Register the ramp program (max. seven steps, each step comprising a ramp
rate and soak value) in advance to the Step Ladder Program block. The Step
Ladder Program is used in combination with the run/stop command from the
Step Ladder Program block and the arrival at final signal to the Step Ladder
Program block.
PID
PV
MV
Ramp program
RSP
Time
SP
AI 4-point Terminal
Block Model 586
PV
Basic PID
Block Model 011
Analog input
MV
Analog output
Ramp Program
Block Model 155
Step Ladder Program
Block Model 301
RSP
Operation instruction
Arrival at final st200
AO 4-point
Terminal Block
Model 587