![Omron CJ1M-CPU21 Operation Manual Download Page 94](http://html1.mh-extra.com/html/omron/cj1m-cpu21/cj1m-cpu21_operation-manual_742493094.webp)
65
PLC Setup Settings
Section 4-2
Pulse Output 1 Search Compensation Value 1 (Origin Compensation)
Note
When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 1 Origin Search Acceleration Rate
Note
When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 1 Origin Search Deceleration Rate
Note
When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 1 Positioning Monitor Time
Note
When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Programming
Console setting
address
Settings
Default
Function
Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word
Bits
282
00 to 15 80000000 to
7FFFFFFF hex
(See note.)
---
Sets the pulse output 1 origin com-
pensation (-2,147,483,648 to
2,147,483,647).
---
When operation
starts
283
00 to 15
Programming
Console setting
address
Settings
Default
Function
Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word
Bits
284
00 to 15 Pre-Ver. 2.0 CPU
Units: 0001 to
07D0 hex
CPU Units Ver.
2.0: 0001 to FFFF
hex
(See note.)
---
Sets the origin search acceleration
rate for pulse output 0.
Pre-Ver. 2.0 CPU Units:
1 to 2,000 pulses/4 ms
CPU Units Ver. 2.0:
1 to 65,535 pulses/4 ms
---
When operation
starts
Programming
Console setting
address
Settings
Default
Function
Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word
Bits
285
00 to 15 Pre-Ver. 2.0 CPU
Units: 0001 to
07D0 hex
CPU Units Ver.
2.0: 0001 to FFFF
hex
(See note.)
---
Sets the origin search deceleration
rate for pulse output 0.
Pre-Ver. 2.0 CPU Units:
1 to 2,000 pulses/4 ms
CPU Units Ver. 2.0:
1 to 65,535 pulses/4 ms
---
When operation
starts
Programming
Console setting
address
Settings
Default
Function
Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word
Bits
287
00 to 15 0000 to 270F hex
(See note.)
0000
hex
Specifies the positioning monitor time
(0 to 9,999 ms) for pulse output 1.
---
When operation
starts
Summary of Contents for CJ1M-CPU21
Page 1: ...Cat No W395 E1 03 CJ series Built in I O CJ1M CPU21 22 23 CJ1M CPU Units...
Page 2: ...CJ series Built in I O CJ1M CPU21 22 23 CPU Units Operation Manual Revised August 2004...
Page 3: ...iv...
Page 19: ...xx...
Page 79: ...50 Wiring Examples Section 3 3...
Page 217: ...188 Origin Search and Origin Return Functions Section 6 3...
Page 220: ...191 Built in Outputs Section 7 1...
Page 247: ...218 Built in Outputs Section 7 1...
Page 251: ...222 Combinations of Pulse Control Instructions Appendix A...
Page 255: ...226 Using Pulse Instructions in other CPU Units Appendix B...
Page 263: ...234 Index...
Page 265: ...236 Revision History...