![Omron CJ1M-CPU21 Operation Manual Download Page 204](http://html1.mh-extra.com/html/omron/cj1m-cpu21/cj1m-cpu21_operation-manual_742493204.webp)
175
Origin Search and Origin Return Functions
Section 6-3
Operating Mode 1 without Origin Proximity Input Signal Reverse (Origin
Detection Method Setting = 1)
Depending on the length of the deceleration time, the stopping position may
change when the Origin Input Signal is detected during deceleration.
Operating Mode 2 (with Error Counter Reset Output, with Positioning
Completed Input)
This operating mode is the same as mode 1, except the Positioning Com-
pleted Signal (INP) from the Servo Driver is used. With origin search 0, the
Positioning Completed Signal from the Servo Driver connects to IN4. With ori-
gin search 1, it connects to IN5.
If origin compensation is not being applied, the Positioning Completed Signal
is checked after the Error Counter Reset Output. If origin compensation is
1
1
0
0
CCW
CCW
CW
CW
Origin Proximity
Input Signal
Origin Input Signal
(Phase-Z signal)
Pulse output
Verify that the Origin Proximity Input
Signal's dog setting is long enough
(longer than the deceleration time.)
Origin Input
Signal is
ignored during
deceleration.
Motor stopped by an Origin
Input Signal received after
deceleration.
Starts when
ORG(889) is
executed.
Stop
Ideal time for the Origin Proximity Input
Signal to go OFF.
(Settings when the
deceleration time is short)
Stop (See note.)
Starts when ORG(889)
is executed.
Note:
The Origin Input Signal can be detected immediately
after the Origin Proximity Input Signal goes from ON
to OFF if the deceleration time is short, e.g., starting
from within the Origin Proximity Input Signal.
1
1
0
0
CCW
CCW
CW
CW
Origin Proximity
Input Signal
Origin Input Signal
(Phase-Z signal)
(The deceleration time is
relatively long in this case.)
Pulse output
(The deceleration time is short
in this case.)
Origin Input
Signal is
ignored during
deceleration.
Motor stopped by an Origin
Input Signal received after
deceleration.
Starts when
ORG(889) is
executed.
Stop
Motor stopped by an
Origin Input Signal
received after
deceleration.
Starts when
ORG(889)
is executed.
Stop
Summary of Contents for CJ1M-CPU21
Page 1: ...Cat No W395 E1 03 CJ series Built in I O CJ1M CPU21 22 23 CJ1M CPU Units...
Page 2: ...CJ series Built in I O CJ1M CPU21 22 23 CPU Units Operation Manual Revised August 2004...
Page 3: ...iv...
Page 19: ...xx...
Page 79: ...50 Wiring Examples Section 3 3...
Page 217: ...188 Origin Search and Origin Return Functions Section 6 3...
Page 220: ...191 Built in Outputs Section 7 1...
Page 247: ...218 Built in Outputs Section 7 1...
Page 251: ...222 Combinations of Pulse Control Instructions Appendix A...
Page 255: ...226 Using Pulse Instructions in other CPU Units Appendix B...
Page 263: ...234 Index...
Page 265: ...236 Revision History...