113
ACCELERATION CONTROL: ACC(888)
Section 5-8
■
Independent Mode Positioning
When independent mode operation is started, pulse output will be continued
until the specified number of pulses has been output.
The deceleration point is calculated from the number of output pulses and
deceleration rate set in S and when that point is reached, the frequency is
decreased every pulse control period (4 ms) at the deceleration rate specified
in S until the specified number of points has been output, at which point pulse
output is stopped.
Note
1.
Pulse output will stop immediately if the CPU Unit is changed to PRO-
GRAM mode.
2.
The number of output pulses must be set each time output is restarted.
3.
The number of output pulses must be set in advance with PULS(881).
Pulses will not be output for ACC(888) if PULS(881) is not executed first.
Stopping
pulse output
To stop
pulse out-
put
Immediate stop
Immediately stops
pulse output.
ACC(888)
(Continu-
ous)
↓
INI(880)
(Continu-
ous)
To stop
pulse out-
put
Immediate stop
Immediately stops
pulse output.
ACC(888)
(Continu-
ous)
↓
SPED(885)
(Continu-
ous, target
frequency of
0)
To stop
pulse out-
put
smoothly
Decelerating to a
stop
Decelerated pulse
output to a stop.
Note
If ACC(888)
started the
operation, the
original
acceleration/
deceleration
rate will
remain in
effect.
If SPED(885)
started the
operation, the
acceleration/
deceleration
rate will be
invalid and
the pulse out-
put will stop
immediately.
ACC(888)
(Continu-
ous)
↓
ACC(888)
(Continu-
ous, target
frequency of
0)
Operation
Purpose
Application
Frequency changes
Description
Procedure/
instruction
Pulse frequency
Present frequency
Execution of ACC(888) Execution of INI880)
Time
Pulse frequency
Present frequency
Execution of ACC(888)
Execution of SPED(885)
Time
Pulse frequency
Present frequency
Execution of ACC(888)
Execution of ACC(888)
Time
Acceleration/deceleration rate
(value set when starting)
Target frequency = 0
Summary of Contents for CJ1M-CPU21
Page 1: ...Cat No W395 E1 03 CJ series Built in I O CJ1M CPU21 22 23 CJ1M CPU Units...
Page 2: ...CJ series Built in I O CJ1M CPU21 22 23 CPU Units Operation Manual Revised August 2004...
Page 3: ...iv...
Page 19: ...xx...
Page 79: ...50 Wiring Examples Section 3 3...
Page 217: ...188 Origin Search and Origin Return Functions Section 6 3...
Page 220: ...191 Built in Outputs Section 7 1...
Page 247: ...218 Built in Outputs Section 7 1...
Page 251: ...222 Combinations of Pulse Control Instructions Appendix A...
Page 255: ...226 Using Pulse Instructions in other CPU Units Appendix B...
Page 263: ...234 Index...
Page 265: ...236 Revision History...