164
Built-in Outputs
Section 6-2
Restrictions
The following restrictions apply when using S-curve acceleration/deceleration.
Starting Frequency
The starting frequency must be 100 Hz or greater. If the starting frequency is
set to less than 100 Hz, it will automatically be increased to 100 Hz if S-curve
acceleration/deceleration is set.
Target Frequency
S-curve acceleration/deceleration will not be performed if the target frequency
is less than 100 Hz.
6-2-4
Variable Duty Ratio Pulse Outputs (PWM(891) Outputs)
Overview
The PWM(891) instruction is used to generate PWM(891) (Pulse Width Mod-
ulation) pulse outputs with a specified duty ratio. The duty ratio is the ratio of
the pulse's ON time and OFF time in one pulse cycle. The duty ratio can be
changed while pulses are being output.
Bit Allocations
50 Hz
100 Hz
Automatically
increased
to 100 Hz.
Pulse frequency
Time
50 Hz
No
acceleration/deceleration
Code
Word address
Bit
Function
OUT4
CIO 2961
04
PWM(891) output 0
OUT5
05
PWM(891) output 1
Summary of Contents for CJ1M-CPU21
Page 1: ...Cat No W395 E1 03 CJ series Built in I O CJ1M CPU21 22 23 CJ1M CPU Units...
Page 2: ...CJ series Built in I O CJ1M CPU21 22 23 CPU Units Operation Manual Revised August 2004...
Page 3: ...iv...
Page 19: ...xx...
Page 79: ...50 Wiring Examples Section 3 3...
Page 217: ...188 Origin Search and Origin Return Functions Section 6 3...
Page 220: ...191 Built in Outputs Section 7 1...
Page 247: ...218 Built in Outputs Section 7 1...
Page 251: ...222 Combinations of Pulse Control Instructions Appendix A...
Page 255: ...226 Using Pulse Instructions in other CPU Units Appendix B...
Page 263: ...234 Index...
Page 265: ...236 Revision History...