Built-in Inputs
Section 6-1
Restrictions on High-speed Counter Inputs
• The Phase-Z Software reset method cannot be used when high
speed counters 0/1 are operating in Differential Phase or Pulse + Direc-
tion Input Modes and the origin search function is enabled for pulse out-
put 1. The Phase-Z Software reset method can be used when
high speed counters 0/1 are operating in Incrementing or Up/Down Input
Modes.
• General-purpose inputs 8 and 9 cannot be used when high-speed
counter input 0 is being used. Furthermore, general-purpose input 3,
interrupt input 3, and quick-response input 3 cannot be used if the high-
speed counter 0 reset method is set to Phase-Z Software reset.
General-purpose inputs 6 and 7 cannot be used when high-speed
counter input 1 is being used. Furthermore, general-purpose input 2,
interrupt input 2, and quick-response input 2 cannot be used if the high-
speed counter 0 reset method is set to Phase-Z Software reset.
Specifications
Item
Specification
Number of high-speed counters
2 (High-speed counters 0 and 1)
Allocated data area
CIO 2960 (The bits actually used depend on the pulse input mode selected.)
Pulse input mode
(Selected in the PLC Setup)
Differential phase
inputs
Up/down inputs
Pulse + direction
inputs
Increment inputs
Input pin
allocation
High-speed
counter 0
High-speed
counter 1
24 V: 25
LD+: 27
0 V/LD
−
: 29
24 V: 19
LD+: 21
0 V/LD
−
: 23
Phase-A input
Increment pulse
input
Pulse input
Increment pulse
input
24 V: 26
LD+: 28
0 V/LD
−
: 30
24 V: 20
LD+: 22
0 V/LD
−
: 24
Phase-B input
Decrement pulse
input
Direction input
---
24 V: 8
LD+: 10
0 V/LD
−
: 12
24 V: 7
LD+: 9
0 V/LD
−
: 11
Phase-Z input
Reset input
Reset input
Reset input
Input method
Differential phase
4X (Fixed)
Single-phase input
+ Direction input
Single-phase input
X 2
Single-phase input
Response
frequency
Line-driver inputs
50 kHz
100 kHz
100 kHz
100 kHz
24-V DC inputs
30 kHz
60 kHz
60 kHz
60 kHz
Counting mode
Linear mode or Ring mode (Select in the PLC Setup.)
Count value
Linear mode: 80000000 to 7FFFFFFF hex
Ring mode: 00000000 to Ring SV
(The Ring SV is set in the PLC Setup and the setting range is 00000001 to
FFFFFFFF hex.)
High-speed counter PV storage loca-
tions
High-speed counter 0:
A271 (leftmost 4 digits) and A270 (rightmost 4 digits)
High-speed counter 1:
A273 (leftmost 4 digits) and A272 (rightmost 4 digits)
Target value comparison interrupts or range comparison interrupts can be exe-
cuted based on these PVs.
Note
The PVs are refreshed in the overseeing processes at the beginning of each cycle.
Use the PRV(881) instruction to read the most recent PVs.
Data format: 8 digit hexadecimal
Range in linear mode: 80000000 to 7FFFFFFF hex
Range in ring mode: 00000000 to Ring SV
Summary of Contents for CJ1M-CPU21
Page 1: ...Cat No W395 E1 03 CJ series Built in I O CJ1M CPU21 22 23 CJ1M CPU Units...
Page 2: ...CJ series Built in I O CJ1M CPU21 22 23 CPU Units Operation Manual Revised August 2004...
Page 3: ...iv...
Page 19: ...xx...
Page 79: ...50 Wiring Examples Section 3 3...
Page 217: ...188 Origin Search and Origin Return Functions Section 6 3...
Page 220: ...191 Built in Outputs Section 7 1...
Page 247: ...218 Built in Outputs Section 7 1...
Page 251: ...222 Combinations of Pulse Control Instructions Appendix A...
Page 255: ...226 Using Pulse Instructions in other CPU Units Appendix B...
Page 263: ...234 Index...
Page 265: ...236 Revision History...