5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
128
7545652/00 EN
VACUTAP
®
VR-Ex
5.4.1.4 Inserting on-load tap-changer into supporting structure
1.
NOTICE!
Tensile forces can lead to damage and malfunctions on the on-
load tap-changer. Using spacers, insert on-load tap-changer vertically into
supporting structure (maximum 1° deviation from the vertical) so that the
on-load tap-changer reaches its final installation height and only has to be
raised a maximum of 5 to 20 mm once the tap winding and on-load tap-
changer take-off lead have been connected and the bell-type tank fitted.
Figure 133: On-load tap-changer with spacers on supporting structure