5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
157
7545652/00 EN
VACUTAP
®
VR-Ex
3. Fasten oil suction pipe to mounting bracket with cable tie provided. Turn
the cable tie so the closure is facing in toward the mounting bracket.
Figure 174: Cable tie
5.4.7.5 Inserting tap position indicator disk
Due to the coupling pin, the tap position indicator disk can only be installed
when in the correct position.
► Place tap position indicator disk on indicator drive shaft, slide spring clip
on to shaft end.
Figure 175: Tap position indicator disk
5.4.7.6 Securing on-load tap-changer head cover
NOTICE
Damage to the on-load tap-changer!
A missing or damaged o-ring as well as unclean sealing surfaces lead to in-
sulating fluid escaping and therefore to damage to the on-load tap-changer.
► Ensure that the o-ring is positioned untwisted in the on-load tap-changer
head cover.
► Ensure that the o-ring does not become damaged when mounting the
cover.
► Ensure that the sealing surfaces on the on-load tap-changer head cover
and on-load tap-changer head are clean.