5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
143
7545652/00 EN
VACUTAP
®
VR-Ex
NOTICE
Damage to the on-load tap-changer!
Small parts in the oil compartment may block the diverter switch insert,
thereby damaging the on-load tap-changer.
► Ensure that parts do not fall into the oil compartment.
► Check that all small parts are accounted for.
1. Ensure that the inspection window is sealed off with the cover.
2. Remove the screws and washers from the on-load tap-changer head
cover.
Figure 148: On-load tap-changer head cover
3. Remove on-load tap-changer head cover.
Figure 149: On-load tap-changer head cover
5.4.5.2.3 Opening kerosene drain plug
►
NOTICE!
Never remove the kerosene drain plug completely. Only un-
screw the kerosene drain plug between the oil compartment base and se-
lector gear clockwise until it starts to become hard to open.