5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
152
7545652/00 EN
VACUTAP
®
VR-Ex
5.4.7.2 Positioning top part of on-load tap-changer head on bell-type tank
1.
NOTICE!
Unsuitable gaskets may lead to oil escaping and therefore to
damage to the on-load tap-changer. Place a gasket
suitable for the in-
sulating fluid used on the mounting flange
. Clean the sealing surfaces
on the mounting flange and on-load tap-changer head.
Figure 165: Mounting flange with gasket