5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
99
7545652/00 EN
VACUTAP
®
VR-Ex
5.3.6.2.1.4 Lifting out diverter switch insert
1.
CAUTION!
Danger of lacerations when turning the coupling tube with-
out an operating wrench. If the markings on the coupling flange and on-
load tap-changer head are not aligned, turn the coupling tube so that the
markings align, either by directly turning the shielding ring while wearing
gloves or by using an operating wrench.
Figure 99: Aligning the coupling tube
2. Insert the lifting gear in the eyebolts of the coupling tube and position ver-
tically above the diverter switch insert.
3. Lift the diverter switch insert slowly and vertically out of oil compartment,
ensuring that the protective ring on the indicator drive shaft does not be-
come detached when doing so.
Figure 100: Diverter switch insert