5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
131
7545652/00 EN
VACUTAP
®
VR-Ex
4. Close the screening caps and make sure they are seated correctly. The
screw head and nut must be fully covered.
Figure 136: Selector connection contacts
5.4.2.2 Change-over selector connection contacts for reversing change-over
selector connection
NOTICE
Damage to the on-load tap-changer!
Tap-winding connecting leads situated too closely to the change-over selec-
tor's moving parts block the change-over selector and therefore result in
damage to the on-load tap-changer.
► Tap-winding connecting leads in the area of the change-over selector
have to be routed such that they are at a sufficient distance from the
change-over selector's moving parts.