5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
103
7545652/00 EN
VACUTAP
®
VR-Ex
3.
CAUTION!
Danger of lacerations when turning the coupling tube with-
out an operating wrench. If the markings on the diverter switch insert are
not aligned, turn the coupling tube so that the markings align, either by di-
rectly turning the shielding ring while wearing gloves or by using an oper-
ating wrench. Switch over the diverter switch insert if necessary.
Figure 104: Markings on the diverter switch insert
4. Attach lifting gear to diverter switch insert and position diverter switch in-
sert over oil compartment.