8 Technical data
Maschinenfabrik Reinhausen GmbH 2020
230
7545652/00 EN
VACUTAP
®
VR-Ex
8.2 Technical data for protective relay
The technical data for the protective relay RS 2001-Ex is listed in the follow-
ing. In accordance with DIN EN 60255-1, operational accuracy = base accu-
racy
Housing
Outdoor model
Degree of protection
IP 66
Relay actuation
Flap valve with aperture
Vibration immunity
up to max. 3g
Weight
approx. 3.5 kg
Oil flow speed of available types when
tripped (oil temperature 20 °C)
0.65 ±0.15 m/s
1.20 ±0.20 m/s
3.00 ±0.40 m/s
4.80 ±0.60 m/s
Table 21: General technical data
Tripping circuit
The protective relay can be supplied with two independent dry-reed mag-
netic switches. These can be designed as normally open (NO) or normally
closed (NC) contacts (see dimensional drawing supplied).
Electrical data
DC switching capacity
1.2 W…200 W
AC switching capacity (50 Hz)
1.2 VA…400 VA
Switching voltage AC/DC
24 V…250 V
Switched current AC/DC
4.8 mA…2 A
Table 22: Electrical data
Switching capacity (switching load on an off)
Minimum switched current AC/DC (low-
est voltage)
50 mA (at 24 V)
Minimum switched current AC/DC (high-
est voltage)
4.8 mA (at 250 V)
Maximum switched current DC (highest
current)
1.6 A (at 125 V with L/R = 40 ms)
Maximum switched current DC (highest
voltage)
0.9 A (at 250 V with L/R = 40 ms)
Maximum switched current AC (highest
current)
2 A (at 125 V with cos φ = 0.6)
Maximum switched current AC (highest
voltage)
1.6 A (at 250 V with cos φ = 0.6)
Switching operations
1,000 cycles
Table 23: Switching capacity (switching load on an off)