5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
153
7545652/00 EN
VACUTAP
®
VR-Ex
2. Lower and position the top part of the on-load tap-changer head on
mounting flange so that the triangular markings, pins and mounting holes
on the top part and bottom part of the on-load tap-changer head are
aligned.
Figure 166: Markings and aligning pins
5.4.7.3 Connecting on-load tap-changer to top part of on-load tap-changer
head
NOTICE
Incorrectly lifting the on-load tap-changer will damage it!
If the connection screws of the supporting flange are used to lift the on-load
tap-changer, the screws may be damaged, which makes it impossible to
properly screw the on-load tap-changer and the on-load tap-changer head
together!
► Always lift the on-load tap-changer with the specified lifting traverse, and
never with the connection screws of the supporting flange.
1.
NOTICE!
Damage to the on-load tap changer due to escaping insulating
fluid. Ensure that the seal in the oil compartment is clean, intact, and not
twisted.