5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
177
7545652/00 EN
VACUTAP
®
VR-Ex
5.5.2.2 Checking function of protective relay
Check the function of the protective relay before installing it in piping be-
tween the on-load tap-changer head and the oil conservator. The associated
contact positions for checking electrical continuity are shown in the dimen-
sional drawing provided.
1. Loosen the three screws on the terminal box cover and lift off the terminal
box cover.
Figure 198: Terminal box cover
2. Remove the slotted head screw for potential tie-in and remove the termi-
nal box cover with wire.
Figure 199: Terminal box cover
NOTICE
Damage to protective relay!
Damage to protective relay resulting from improper operation!
► Never press both test buttons at the same time.