5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
130
7545652/00 EN
VACUTAP
®
VR-Ex
5.4.2 Connecting the tap winding and on-load tap-changer take-off
lead
NOTICE
Damage to the on-load tap-changer!
Connecting leads that place mechanical strain on the on-load tap-changer
will damage the on-load tap-changer.
► Establish connections carefully.
► Do not twist connection contacts.
► Connect connecting leads without warping or deforming.
► If necessary, use an expansion loop for connecting leads.
► Fit screening caps provided to screw connections.
The tap winding and on-load tap-changer take-off lead must be connected in
accordance with the connection diagram included with the delivery.
5.4.2.1 Selector connection contacts
1. Fasten tap-winding connecting leads with cable shoes and M12 screws as
specified in the connection diagram provided (cable shoes and fastening
materials are not included in the delivery scope). The through-holes of the
connection contacts are horizontal as standard.
2. Make sure that the tap-winding connecting leads are not exerting any me-
chanical loads on the selector.
3. Take suitable measures to ensure that every screw connection cannot
come loose or settle (e.g. by using clamping washers). Attach the screen-
ing caps as shown in the illustration.