5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
141
7545652/00 EN
VACUTAP
®
VR-Ex
1. Check that the feather key is securely positioned in the adapter shaft.
Where necessary, use Vaseline to secure the feather key against falling
out.
Figure 145: Feather key
2. Position the on-load tap-changer head cover on the on-load tap-changer
head in such a way that the red triangular markings on the on-load tap-
changer head and the on-load tap-changer head cover are aligned.
Figure 146: On-load tap-changer head cover with o-ring